121
- The exposed conductor ground plate, or
the cumulative total area of multiple
through-hull fittings and other exposed
underwater metal objects tied into the
grounding system, needs to be of suffi-
cient size to ensure a low-resistance elec-
trical connection to earth ground. The
ABYC recommends at least 1 square foot
of surface area in salt water, which will
generally work for everything but SSB.
SSB manufacturers generally recommend
at least 1 square meter or yard of exposed
surface area. Since fresh water is less elec-
trically conductive than salt water, several
square feet of surface area should be used
for lightning protection. - To reduce the risk of the lightning “side
flashing” as it seeks a path to ground,
heavy metal objects in proximity to a
lightning conductor should be electrically
bonded to the lightning conductor. Also,
lightning tends to jump out of “corners”
created in the lightning ground wiring
system, so minimize sharp bends.
The Elements of a Lightning
Protection System
The basic elements of an LPS are shown in the
illustration. The primary conductor (also
called a down conductor) from the masthead
must have the equivalent conductivity of a
piece of 4 AWG (21 mm^2 ) wire. You can
achieve this by using an aluminum spar as the
conductor. Carbon fiber spars are considered
nonconductive for this purpose, so 4 AWG
wire needs to be added. At the upper end, the
conductor must terminate at what the ABYC
technical report calls an air terminal—in other
words, a lightning rod. The air terminal
should be the highest point on the mast by at
least 6 inches (150 mm).
The down conductor must be tied directly
to a grounding plate (or its equivalent) of at
grounding systems
least 1 square foot in surface area. You can
achieve equivalency in exposed surface area by
tying in other underwater metal objects such
as rudders, metal keel ballasts, through-hull
fittings, and the like to the system, but you
should never connect the down conductor
directly to a through-hull fitting. If you do,
and lightning strikes your boat, the strike may
blow the fitting out through the bottom of the
boat. A tinned copper distribution bus bar
makes a good link for the system if multiple
underwater metal objects are connected
Air terminal
Parallel path Parallel path
Bonding
conductors
(6 AWG)
Engine
Metal tank
Immersed
ground plate
or strip (1 sq. ft.)
4 AWG conductor
short as possible with
8" min. radius bends
Primary
lightning
conductor
(4 AWG)
Secondary
lightning
conductor
(6 AWG)
The essential elements of a lightning protection system. (Reprinted with
permission from Boatowner’s Illustrated Electrical Handbook,second
edition, by Charlie Wing)