Advanced Marine Electrics and Electronics Troubleshooting A Manual for Boatowners and Marine Technicians

(Barry) #1

52 electrical systems troubleshooting


Expected Possible Possible
Measurement Result Problem Causes Solutions
Line voltage 108—132 VAC High/low Too much load on Redistribute loads on the
120 VAC the circuit. circuit.
Line voltage 220 AC 198—242 VAC High-resistance Locate high-resistance
connection within connection/device and
the circuit or at repair/replace.
the panel.
Supply voltage too Consult power company.
high/low.
Neutral-ground < 2 VAC Voltage High G—N > Current leaking from Identify source of leakage:
voltage 2 VAC neutral to ground. multiple bonding points,
equipment, or devices.
Unbalanced three- Check load balance and
phase system. redistribute load.
Triplen harmonics Oversize neutral to
returning on neutral impedance. Reduce harmonic
in three-phase effect via filter or other
system. methods.
Peak voltage 153—185 VAC High/low Supply voltage too Consult power company.
120 VAC peak voltage high/low.
Peak voltage 280—242 VAC High peak loads on Evaluate number of electronic
220 VAC line caused by devices on circuit and
electronic equipment redistribute if necessary.
on line.
Frequency 60 Hz High/low Supply frequency too Consult power company.
frequency high/low.
Source:Ideal Industries, Inc.

Voltage Troubleshooting Tips

TABLE
4-1

Physically check these possibilities and repair
or replace cables or components as needed.
This is also an area where the infrared heat
gun (see Chapter 5) can be useful in finding
the hot spot in the circuitry. Use Table 4-2 to
help you troubleshoot voltage drop problems.

Impedance Measurements
To further assist you in troubleshooting exces-
sive voltage drop, the SureTest can measure
the exact impedance (resistance) in each of the
three conductors in a circuit. Again, I know of
no other tool that has this capability.

If measured voltage drop is more than 5%,
a problem exists. Using the meter’s arrow keys,
scroll through the menu to read and compare
the impedance values for the hot, neutral, and
ground conductors. What you are looking for
here is parity among the conductors.
If impedance in one conductor is signifi-
cantly higher than another, then you’ve narrowed
down the problem. Again, loose or corroded
connections are the most probable cause, and
you must now physically search out the culprit.
If all the conductors read high, then the
cabling is probably undersized. Keep in mind
Free download pdf