Advanced Marine Electrics and Electronics Troubleshooting A Manual for Boatowners and Marine Technicians

(Barry) #1
significant when you consider circuit breaker
ratings, because if the ASCC is greater than the
ampere interrupting capacity (AIC) rating for a
breaker or fuse, the device may not function
when a short circuit occurs. Instead, in the case
of the breaker, the contacts can be welded
closed, and in the case of a fuse, the fuse element
can arc.
ABYC Standard E-11 establishes AIC limits
for AC and DC breakers and fuses, as shown in
the ABYC table below. Simply put, whatever
readings the SureTest gives you on this test
sequence, you need to be sure they are below
the AIC ratings shown in the table. Typical AIC
ratings for circuit breakers used in AC applica-
tions will exceed this value, in my experience.
For example, on docks I’ve checked, the ASCC
readings were well below the AIC ratings on the
breakers used due to the voltage drop induced
by the wire gauge and length of wire runs typi-
cal of marina and dock wiring schemes. Com-
mon ASCC readings on docks I’ve checked fall
in the 1,000 to 2,000 amp range.

GFCI and GFP Testing
One more useful SureTest function is testing
GFCI and GFP devices. (GFPs are also

54 electrical systems troubleshooting


known as RCDs—residual current devices,
and EPDs—equipment protecting devices.)
The ABYC describes GFCI devices as those
intended to protect people from shock haz-
ards associated with AC faults, and GFP
devices as those intended to protect equip-
ment from damage. The big difference in this
application between a SureTest and a $5 LED
circuit tester is that a SureTest will measure
both the trip rate (in milliamps, mA) and the
trip time for the GFCI or GFP. This informa-
tion can warn you of the device’s imminent
failure. Considering the statistically high fail-
ure rate of GFCIs, particularly in marine
applications (more on GFP testing in a
minute), the ability to perform these tests is
of paramount importance.
During the test, the instrument creates a
small but steadily increasing current imbal-
ance between the hot and neutral conductors.
The GFCI should respond by tripping
between 4 mA and 7 mA. Most GFCIs that
I’ve checked trip at 7 mA if all is well. Note
that the nominal rating of GFCIs in North
America is 5 mA, but as with all breaker-type
devices, the nominal rating and the actual trip
rate are always different values.

NOTES: 1. The main circuit breaker shall be considered to be the first circuit breaker connected to a source of AC power.
All subsequent breakers, including sub-main breakers connected in series with a main circuit breaker, shall be consid-
ered to be branch circuit breakers.



  1. A fuse in series with, and ahead of, a circuit breaker may be required by the circuit breaker manufacturer to achieve
    the interrupting capacity in TABLE V-B.


The circuit breaker interrupting capacity for systems over 50 V from ABYC Standard E-11. (Courtesy ABYC)
Free download pdf