Dave Gerr - Boat Mechanical Systems Handbook-How to Design, Install, and Recognize Proper Systems in Boats

(Rick Simeone) #1
ventilation duct is complex, but a simple
approximation can be used for small, ducted
systems up to about 14 feet (4.3 m) long, as
shown in Table 14-4.
Example:In the master stateroom from
earlier, we found we needed between 46.8 and
62.4 cfm, say 55 cfm. This stateroom is entirely
below the aft saloon. The windows on the hull
side are too close to the waterline to open
safely. Vent ducts can run down from the cabin
roof. They enter from a mushroom vent on the
roof and go straight down the cabin side for
9 feet to exit through louver grilles via a 90-
degree bend. Percent loss of blower capacity is

9 feet×2% per foot =18%
90-degree bend =10%
Louver grille =20%
Total approximate loss =58%
Effective vent output =100% – 58% =42% of
blower’s rated cfm output

Required blower capacity is then

55 cfm ÷ 0.42 =131 cfm

NOTE: If the approximate loss is over
80 percent, this simple approach is not ade-
quate, and a detailed duct analysis is required.
The 131 cfm could be handled by a stan-
dard 3-inch squirrel-cage blower (Figure 14-10),
rated at 150 cfm.
Or
Example:In the master stateroom from
earlier, we found we needed between 79
m^3 /hr. and 106 m^3 /hr., say 93 m^3 /hr. This state-
room is entirely below the aft saloon. The
windows on the hull side are too close to the
waterline to open safely. Vent ducts can run

PART FIVE:VENTILATION, AIR-CONDITIONING, AND HEATING


TABLE 14-4.ABYC ESTIMATED EFFECT OF
BLOWER SYSTEM COMPONENTS

Percent Loss of Blower
Item Rated Capacity
Ducting 2% per ft.of length,
or 6.56% per m of
length
Ducting Bends—90° 10% each bend
Clamshell Vent Intake 20%
Louver 20%
Screen—^1 / 4 -in.
(6.35 mm) mesh 10%

Figure 14-10. Squirrel-cage blower
(Courtesy Vetus Den Ouden)

down from the cabin roof. They enter from a
mushroom vent on the roof and go straight
down the cabin side for 2.74 meters to exit
through louver grilles via a 90-degree bend.
Percent loss of blower capacity is

2.74 m×6.56% per m =18%
90-degree bend =10%
Louver grille =20%
Total approximate loss =58%
Effective vent output =100% – 58% =42%
of blower’s rated cfm output

Required blower capacity is then

93 m^3 /hr. ÷ 0.42 =221 m^3 /hr.
221 m^3 /hr. ÷ 60 sec./hr. =3.7 m^3 /min.

NOTE: If the approximate loss is over
80 percent, this simple approach is not ade-
quate, and a detailed duct analysis is required.
The 3.7 m^3 /min. could be handled by a
standard 7.6 cm squirrel-cage blower, rated at
255 m^3 /hr. or 3.7 m^3 /min.
As a rule, avoid long duct runs in simple
ventilation systems, particularly horizontal
ones, unless a complete, detailed duct analy-
sis is performed. One 110-foot (33.5 m) mo-
toryacht I surveyed had a vent duct running
from the crew utility room, with washer and
dryer, about 70 feet (21 m) aft to vent into the
engine room. No calculations were done on
the duct blower, which was so underpowered
that airflow was too slow. Not only was this
Free download pdf