Burying Electrical Cable


6"

Galvanized metal conduit

Underground feeder cable

Underground feeder cable

PVC conduit

12"

18"

24"

A reader asked us to shed some light on the depth requirements for
burying electrical cable. Al Hildenbrand, one of our electrical experts,
explained the rules this way:
Q OPTION 1: If you don’t want to dig deep trenches, you can bury indi-
vidual conductors inside RMC (rigid metal conduit) at a depth of 6 in.
Q OPTION 2: You can direct-bury UF-B (underground feeder) at a
depth of 12 in. In this case, PVC conduit must run to the full 12-in.
depth. Also, the circuit must be limited to 15 or 20 amps and 120 volts,
AND the wiring must have GFCI (ground-fault circuit interrupter) pro-
tection before the branch circuit enters the ground.
Q OPTION 3: When either the current is greater than 20 amps or the
voltage is greater than 120 volts, or both, the PVC must run to a depth
RILQb*)&,SURWHFWLRQGRHVQRWDIIHFWWKLVUXOH
Q OPTION 4: To direct-bury any circuit that isn’t protected by a GFCI,
the trench must be 24 in. deep. A circuit greater than 20 amps, greater
than 120 volts, or both, without conduit, requires a depth of 24 in.

of the platform and cut the fence
slightly shorter than the platform.
Next, glue the fence and hook to
opposite ends and sides of the
platform as shown. This allows the
bench hook to grab the front edge

of your workbench. Hook it on the
front edge of your bench for use
with a saw that cuts on the push
stroke, or on the back of the bench
for a saw that cuts on the pull
stroke.

No. 4 No. 3 No. 2

No.1

FOR A PUSH SAW FOR A PULL SAW

Platform

Fence

Hook

Fence

Hook
Free download pdf