2007-2008 Turf Catalog

(Rick Simeone) #1
Commercial Pump Stations
Leading Edge Technology

Commercial Pump Stations

Number of Pump Flow Range hp Manifold
Pumps Model (GPM) Range Size
2 CR 3 0 - 40 1 - 3 2" NPT
CR 5 0 - 80 11 ⁄ 2 - 5 2" NPT
CR 10 0 - 120 11 ⁄ 2 - 7^1 ⁄ 2 21 ⁄ 2 " NPT
CR 15 0 - 200 5 - 15 4" ANSI
CR 20 0 - 260 5 - 15 4" ANSI
CR 32 0 - 360 5 - 25 4" ANSI
CR 45 0 - 560 71 ⁄ 2 - 30 6" ANSI
CR 64 0 - 800 71 ⁄ 2 - 40 6" ANSI
CR 90 0 - 1100 15 - 50 6" ANSI
3 CR 3 0 - 66 1 - 3 2" NPT
CR 5 0 - 120 11 ⁄ 2 - 5 2.5" NPT
CR 10 0 - 180 11 ⁄ 2 - 7^1 ⁄ 2 3" NPT
CR 15 0 - 320 5 - 15 4" ANSI
CR 20 0 - 400 5 - 15 4" ANSI
CR 32 0 - 600 5 - 25 6" ANSI
CR 45 0 - 850 71 ⁄ 2 - 30 6" ANSI
CR 64 0 - 1200 71 ⁄ 2 - 40 8" ANSI
CR 90 0 - 1800 15 - 50 8"ANSI
4 CR 3 0 - 100 1 - 3 2.5" NPT
CR 5 0 - 170 11 ⁄ 2 - 5 3" NPT
CR 10 0 - 240 11 ⁄ 2 - 7^1 ⁄ 2 4" ANSI
CR 15 0 - 450 5 - 15 6" ANSI
CR 20 0 - 550 5 - 15 6" ANSI
CR 32 0 - 800 5 - 25 6" ANSI
CR 45 0 - 1100 71 ⁄ 2 - 30 8" ANSI
CR 64 0 - 1600 71 ⁄ 2 - 40 10" ANSI
CR 90 0 - 2200 15 - 50 10" ANSI

Commercial Irrigation and Water Features Flow Range and Horsepower


Variable Frequency Drive (VFD) Multi-Pump Stations


■ Custom designed multi-pump systems that maintain constant
pressure for variable flow for booster, flooded suction, and suction
lift applications.


■ Single source manufacturing with 316SS suction and discharge
headers, 304SS pump station skid and control panel stand,
industrial grade vertical multi-stage centrifugal pumps, and the
MPC advanced pump station controller.


■ Twice the industry standard warranty at 24 months from start-up or
30 months from the date of shipment.


Benefits



  • Site-serviceable cartridge style mechanical seal prevents removing or
    disassembling pump station enclosure, piping, or motor (if 15hp or
    greater) significantly reducing pump station downtime.

  • Automatic pump start and cascade control rotation ensures evenly
    distributed run-time between all pumps, motors, and VFDs extending
    the pump station operational life.

  • Stop Function ensures the pump automatically stops when flow drops
    below operator selected value. This feature assures the pump is not
    subject to overheating and the subsequent risk of shaft seal damage.

  • Multi-pump system offers redundancy and back-up capabilities in
    the event of a pump failure.


Operating Range



  • Flow Range: 0 - 2,200 GPM

  • Head Range: 0 - 500 ft

  • hp Range: 1 - 50 hp

  • Maximum Working Pressure: 360 PSIG


Electrical Specifications



  • Input Required: 60 Hz

    • 1 Phase 208/230 Volt

    • 3 Phase 208/230/460/575 Volt




Three Pump VFD Station with MPC Controller

MPC Controller

VM 2 CRE 32 - 3 - 2

How To Specify


Type
Vertical Multistage Pump

# Pumps
2

Model
CRE

Reduced
Vane Stages
2

Flow
m^3 /hr

Stages
3
Free download pdf