Typical examples using dense concrete of calcareous aggregates
(excluding limestone) or siliceous aggregates, eg. flints, quartzites
and granites ~
Column fully exposed ~
35 mm min. concrete cover to reinforcement
300 mm min. each face, 120 minutes fire resistance
450 mm min. each face, 240 minutes fire resistance
Column, maximum 50% exposed ~
200 mm min., 120 minutes fire resistance, 25 mm cover
350 mm min., 240 minutes fire resistance, 35 mm cover
concrete cover to reinforcement
240 minute fire resistant
compartment wall
Column, one face only exposed ~
160 mm min., 120 minutes
fire resistance
240 mm min., 240 minutes
fire resistance
25 mm min. cover
240 minute fire resistant compartment wall
Beam and floor slab ~
125 mm min. thickness reinforced
concrete compartment floor,
120 minutes fire resistance, 35 mm cover
cover
150 mm min., 120 minutes fire resistance, 50 mm cover
240 mm min., 240 minutes fire resistance, 70 mm cover
Reinforced Concrete--Fire Protection