Building Construction Handbook, Eighth Edition

(Nancy Kaufman) #1

Reinforced concrete suspended floors


column


Note: Standard cavity


wall insulated as


required


reinforced concrete


perimeter beam


dovetail channel


support rail


set in concrete


6mm steel angle


bracket, min.


penetration into


Calculated brickwork


galvanised steel


fish-tail tie


sliding brick anchor ~


(ties fit loosely over


guide)


brickwork


movement joint


(^23)
Application † multi-storey buildings, where a traditional brick
fac ̧ade is required.
Brickwork movement † to allow for climatic changes and
differential movement between the cladding and main structure, a
`soft' joint (cellular polyethylene, cellular polyurethane, expanded
rubber or sponge rubber with polysulphide or silicon pointing)
should be located below the support angle. Vertical movement
joints may also be required at a maximum of 12 m spacing.
Lateral restraint † provided by normal wall ties between inner and
outer leaf of masonry, plus sliding brick anchors below the support
angle.
Brickwork Cladding Support System