Institutional and Assembly Stairs ~ Serving a place where a
substantial number of people will gather.


minimum going, 280 mm (may
reduce to 250 mm if the building
floor area <100 m^2 ),
maximum, 340 mm

The maximum pitch for gangways
with seated spectators in assembly
buildings is 35ƒ.

rise 135
to 180 mm

Other stairs ~ All other buildings.


minimum going, 250 mm
maximum, 320 mm

rise 150
to 190 mm

Common to both functional
groups: twice the rise plus
the going, 550 to 700 mm.

Alternative guidance: BS 5395-1: Stairs, ladders and walkways. Code of
practice for the design, construction and maintenance of straight stairs
and winders.
The rise and going in both situations may be subject to the requirements
of Approved Document M: Access to and use of buildings. AD M will take
priority and the following will apply:


Going (external steps) ~ 280 mm minimum (300 mm min. preferred).
Going (stairs) ~ 250 mm minimum.
Rise ~ 170 mm maximum.


Other AD M requirements for stairs:


Avoid tapered treads.
Width at least 1200 mm between walls, strings or upstands.
Landing top and bottom, minimum length not less than stair width.
Handrails both sides; circular or oval preferred as shown on next page.
Door openings onto landings to be avoided.
Full risers, no gaps.
Nosings with prominent colour 55 mm wide on tread and riser.
Nosing projections avoided, maximum of 25 mm if necessary.
Maximum 12 risers; exceptionally in certain small premises 16.
Non-slip surface to treads and landing.