INDOOR AIR POLLUTION 493
air as makeup is supplied to the laboratory space to balance
the air being exhausted. It is good practice to supply a little
less makeup air this way than that being exhausted. A slight
negative pressure will be maintained, drawing air through
door louvers from corridors or adjacent offi ces.
Air exhausted from a hood is never recirculated so that
hood burden goes up. Operating costs can be reduced by
supplying makeup air from an auxiliary source instead from
the cooling system. The air handled is fi ltered and tempered
in winter only. Of the seven basic hood designs, numbers 4d,
4e, and 4f make use of the auxiliary system. An auxiliary
system can be either a central unit or unitary type with an
outside air inlet for each laboratory. Correct selection of the
type of makeup air system can be made only by an engineer-
ing analysis and fl ow sheet of the hood exhaust system.
One of the most important characteristics of an exhaust
system is that at some point the system must end and discharge
to atmosphere. Unfortunately, while the exhaust system has
ended at this point, the problems associated with that exhaust
system may have just begun. If too much air discharged from
an exhaust system is recirculated through the supply system
not much good has been accomplished. If by poor design the
exhaust air is not properly located with respect to the intakes
of other supply systems, potentially disastrous results can
be attained. Many poor designs are commonplace. The real
cure for this type of problem is not higher exhaust velocities,
higher stacks, better weather caps, better separation of dis-
charge and intake openings, or other, although one or more of
these can contribute to the cure. The real remedy must start
back at the source of contamination itself.
Because the pattern of natural air fl ow around buildings
is not predictable, contamination by the location of vent effl u-
ents and air intakes is diffi cult to put to practice. Halitsky^2
(1963) and Clarke^3 (1967) have advanced theoretical
knowledge and rule of thumb that aid greatly in the solution
of such problems.
AIR DISTRIBUTION
In review, air movement within each room of a laboratory
complex must be such that a defi nite fl ow pattern will be
maintained throughout the building along with fl ow from
non-contaminated to potentially contaminated areas. To
bring about this differential fl ow pattern, the nature barriers
between the various classes of rooms will assist. The pattern
will also be assisted by supplying outside clean air to the non-
contaminated and semi-contaminated areas and by exhaust-
ing air only from the moderately and extremely contaminated
areas. In general, supply fans should take suction from the
upper portions of the building. Also, the exhaust fans should
discharge to the outdoors through stacks of varying heights
depending on adjacent structures. To help, the building should
be maintained at a slight positive pressure with respect to the
outdoors. Laboratory rooms should be maintained at a nega-
tive pressure with respect to the surrounding rooms.
Only an adequate supply of makeup air to satisfy exhaust
needs will keep the building in balance. This certainly implies
there must be an excess of supply over exhaust needs. In actual
installations, experience shows that when two fans are exhaust-
ing from the same space with no provision for makeup air, the
stronger fan will take command and outside air will enter the
room through the weaker fan system. When there are multiple
exhaust hoods and no makeup air, with one hood off, outside air
can downdraft through the idle fan. When a fan must exhaust
from a room without makeup, fan capacity will be reduced
from design and will result in less control at the hood.
EXHAUST SYSTEM
The exhaust system being under negative pressure will cause
leakage fl ow to be drawn into the system and contamination
will be confi ned. Best location for an exhaust fan serving
hoods is on the roof. Then all exhaust ductwork will be on
the suction side of the fan and indoors. But this is not always
possible. If the fan location must be indoors, say just above
the hood, then careful attention must be paid to duct tight-
ness on the discharge side. When fl ammable material is han-
dled, mounting fan on roof is a distinct advantage because
explosion-proof construction may not be required of the fan
motor. However, fan wheel should be non-ferrous and inside
casing should be epoxy coated for corrosion protection.
EXHAUST DUCT MATERIALS
In many buildings ductwork is often concealed in ceilings or
inside walls, making duct inspection and replacement a major
problem. Where this condition exists it is reasonable to use
ductwork with long life expectancy. For chemicals used in lab-
oratories, galvanized iron and black iron ductwork are highly
susceptible to corrosion. Stainless steel, transite, polyvinyl
chloride-coated steel or fi berglass- reinforced plastic (FRP)
ductwork will not require early replacement for such corro-
sive service but are costly. Actually, selection of materials
will depend on the nature and concentration of contaminants
or chemical reagents, space conditions, cost, accessibility.
Whatever materials are selected, duct joints must be leaktight
and the ductwork should have ample supports. For best ser-
vice life all longitudinal duct seams should be run along the
top panel. An extensive duct system should have inspection
and cleaning facilities. Ducts that could develop condensa-
tion loading should pitch toward a pocket in the bottom of the
run and be provided with a trapped drain.
Type 316 passive stainless steel may be used for bac-
teriological, radiological, perchloric acid and other general
chemical purposes. 316 stainless steel is easy to work but
is not suitable for chemical hoods handling concentrated
hydrochloric and sulfuric acids.
EXHAUST AIR TREATMENT
Gases that are bubbled through reaction mixtures and then
discharge to the hood are generally, by their nature, reactive
C009_001_r03.indd 493C009_001_r03.indd 493 11/18/2005 10:29:57 AM11/18/2005 10:29:57 AM