494 INDOOR AIR POLLUTION
enough to be completely eliminated by a scrubber of some
design. For materials that are acidic, a simple caustic scrubber
is all that is necessary to assure essentially complete control.
Similarly, for materials of a basic nature, an acid scrubber may
be used to advantage. For those materials that do no react rap-
idly with either caustic or acidic solutions, a column fi lled with
activated charcoal will always provide the desired control.
Perchloric acid is highly soluble in water and hoods
have been developed with packed sections built into the
hood superstructure and provided with water wash rings
in the ductwork downstream of the scrubber to prevent
buildup of perchlorates which are explosive on contact.
Fume hoods handling highly radioactive materials should
have HEPA fi lters upstream and downstream of the hood.
For highly hazardous bacteriological experiments safety can
be achieved only by incineration of the exhaust air stream,
which is heated to about 650°F to destroy the bacteria.
SPECIAL SYSTEMS
Lowered Sash Operation
A hood exhaust fan maintains proper capture velocity when
the sash is wide open, but the exhaust’s hood’s vertically slid-
ing sashes are sometimes lowered to within a few inches of
the work surface when the hood is in operation. A method in
use to reduce waste of conditioned air and also to achieve a
more constant face velocity over the range of sash positions
is the use of a 2-speed fan for each hood. When the sash is
pushed up the fan runs at high speed. A micro-switch mounted
in the hood is tripped by the sash when it is lowered below a
predetermined position. The volume of air the fan will pull
on low speed is adequate to maintain desired face velocity for
the smaller cross-sectional area. The proper placement of the
switch setting can be 50 to 60% of the vertical face opening,
i.e., the fan would go on low speed when the sash is lowered to
50 to 60% of opening. This holds for all exhaust hoods despite
differences in hood dimensions and other variations in exhaust
systems. It has been found to apply equally as well to hoods
with minimum face velocities of 80, 100, and 125 fpm. The
volume of conditioned air that is normally lost is reduced by
about one-third when the sash is below the set point.
In a conventional hood with a single speed fan, the
excessively high face velocities experienced at low sash set-
tings and the cooling effect on the backs of lab personnel
using the hood has an overall adverse effect. Further, still,
when the laboratory technician stands in front of a hood in
operation his body presents an obstruction to the fl ow of
air into the hood. Thus, a low pressure area develops in the
space between the man and the hood. Under certain condi-
tions, the resulting low pressure area can cause fumes to be
aspirated from the hood and out into the room. The reduc-
tion in face velocity using the 2-speed fan reduces the prob-
ability of such a hazardous condition developing.
Type “S” hoods should be provided with fan speeds
so that at no point across the hood face should a velocity
greater than 250 fpm exist. Another way to control this
velocity is to provide by-pass dampers in the exhaust duct
just downstream of the hood itself. By-pass hoods are
made to accomplish this effect by providing this feature in
the hood structure itself.
By-Pass Hoods
These provide for a constant rate of room exhaust and uni-
form face velocities at any door position. They stabilize the
room exhaust and the room they supply. The by-pass may be
an integral part of the hood itself. As the hood door begins to
close, the damper starts to open. Another important aspect
and advantage of the by-pass hood is that the hood interior
is continuously being purged of fumes even while the door
is closed tight. For the by-pass hood see Figure 3.
Supply Air Hoods
Two types are commercially available. The fi rst has auxil-
iary air introduced outside and in front of the sash, normally
from the overhead position. In this design the auxiliary air
supply is drawn into the sash opening as a part of the room
air. Relative cost of this type compared to the conventional is
high. Relative cost of air conditioning is low because amount
of room air exhausted is reduced. Air conditioning effective-
ness, fume removal effectiveness, and convenience to lab
personnel are good. However, acceptability to local authori-
ties should be investigated. See Figure 4(a).
In the second type, auxiliary air is fed directly into the hood
on the inside. Relative cost is high, cost of air conditioning is
low, air conditioning effectiveness is good, but fume removal
effectiveness is poor. Because effective face velocities can drop
TYPICAL BY-PASS HOOD
Safety
Shelf
By-pass
Damper
FIGURE 3
C009_001_r03.indd 494C009_001_r03.indd 494 11/18/2005 10:29:57 AM11/18/2005 10:29:57 AM