Heating Systems 317
U
W = ——
3.4
= 0.3584
= ———
3.4
= 0.1054 watts heat loss
Solution (with insulation):
R = a + b + c + d + e + f
= 0.80 + 0.75 + 0.04 + 0.85 + 0.35 + 11.0
= 13.79
1
U = —
R
1
U = ———
13.79
= 0.0725 Btu per ft^2 per hour per °F
U
W = ——
3.4
= 0.0725
= ———
3.4
= 0.0213 watts heat loss
You can see from the results of this problem that the adding of in-
sulation into the walls of a building has a great effect upon heat loss. The
insulation has a much greater effect in controlling heat loss than do the
construction materials used for the building.