technical NOTES

(Project Pridr) #1
S. N. Description Unit GRR
+SPRS

MV


Drive

Remarks

9 Additional cost due to AC
arrangement

Rs. Lac 7

10 Additional Rotor Cable cost 3.3Kv
HT 300 Sq. mm cable @700 Rs/
Mtr (1000 Mtr 12 Runs)

Rs Lac 7

11 Capital Investment Rs. Lac 153 164
12 Investment Difference SPRS with
MV drive

11


Loss Calculation



  1. Avg. Power Loss across SPRS
    @80% speed (Motor Power
    1536kw/1000 rpm)
    Overall efficiency/loss of SPRS
    solution: Transformer 98.5% *SPRS
    97% of 307KW (i.e. 20 % 1536 KW)

    • slip ring Motor 94.2% of 1536 KW
      Transformer and SPRS have 20%
      rating of Slip ring motor
      So total loss in SPRS and Trans-
      former =




NA


98.5%*97%*307MW (i.e. 20 % of
1536KW) = 13.68KW
Loss in Slip ring motor =
94.2%*1536MW = 89.09 KW
Total loss in SPRS solution(a+b) =
13.68+ 89.08= 102.77 KW = 103KW

103


Avg. Power Loss across MV Drive
@80% speed (Motor Power
1536Kw/1000 rpm/11KV)
Overall efficiency of MVD
solution:
Transformer 98.5% *MVD 98%
*Induction Motor 95.5% = 92.19%
Total loss in MVD solution = 1536
KW* 92.19% = 120 KW

KW NA 120


2 Difference in losses in SPRS and MV drive @ 80% speed KW 17

Fan operating
losses from
40 to 60 % &
95 % to 100%
speed through
GRR is more as
compared to
MV drives