technical NOTES

(Project Pridr) #1

Life cycle analysis summary of air slide blower on VVVFD concept


S. N. Particulars Conventional System VVVFD Concept
1 Initial Investment
i Type of Stator IMCC-HDOL feeder with pro-V VVVFD

ii IMCC HDOL Feeder

01 no HDOL for FAN is
required – IMCC with
pro V

01 no SFU Required for VFD

2 Power Consumption
i Speed Control & Reduction Not Possible Possible 10-110% possible & getting Power Saving

ii

Energy consumption
as per process
requirement

High Energy consumed
as per motor rated KW

Actual Energy consumed
on account of Air Flow &
air Pressure as per Process
requirement.
3 System Installation & Commissioning

i System Installation & Commissioning Time

Large time required, as
more hardware’s in the
system

Less time required, as less
hardware’s in the system
4 Operation & Maintenance
i System reliability Less Efficient compare to VVVFD More Efficient System, 100% Dependency on Drive

ii System Hardware

More Hardware’s with
the system Compare to
VVVFD

Less Hardware’s with
the system Compare to
conventional system
iii System Further optimisation margin Not possible with conventional system Possible with VVVFD System

S. N. Particulars Cost in Lacs
1 Investment against VFD concept 7.69
2 Investment against conventional concept 8.40
3 Lower investment against VVFD concept -0.71
4 Annual benefit against VVVFD considering approx. 10% speed reduction in energy saving 2.31

13.4 Comparison of Conventional System v/s VVVFD Concept.