technical NOTES

(Project Pridr) #1

S. N. Sub Location LED W LED Bat. Idle Hr/Mon


Energy
Cons
(KWh)

Total
Energy
Saving
(KwH)/
Month

Occupancy
Sensor
Required

A MRSS
1 Cable Cellar Room 20 W 7 710 99.4 99.4 2
2 Capacitor Room 40 W 3 700 84 84 1
3 AHU Room 40 W 5 690 138 138 1
4 Panel Room 36 W 12 630 272.16 272.16 2
B Load Center-1
1 Cable Cellar Room 20 W 9 710 127.8 127.8 2
2 Chiller Room 40 W 6 690 165.6 165.6 1
3 AHU Room 40 W 3 690 82.8 82.8 1
4 Panel Room 36 W 26 630 589.68 589.68 3
5 HT Capacitor
Room

40 w 2 700 56 56 1

C Load Center-1A
1 Cable Cellar Room 20 W 13 710 184.6 184.6 2
2 Chiller Room 40 W 6 690 165.6 165.6 1
3 AHU Room 40 W 3 690 82.8 82.8 1
4 Panel Room 36 W 44 630 997.92 997.92 4
D Load Center-2
1 Cable Cellar Room 20 W 33 710 468.6 468.6 2
2 Chiller Room 40 W 15 690 414 414 2
3 AHU Room 40 W 5 690 138 138 1
4 Panel Room 36 W 86 630 1950.48 1950.48 8
5 HT Capacitor
Room

40 W 8 700 224 224 1

E Load Center-3
1 Cable Cellar Room 20 W 22 710 312.4 312.4 2
2 Chiller Room 40 W 20 690 552 552 1
3 AHU Room 36 W 30 690 745.2 745.2 2
4 Panel Room 36 W 88 630 1995.84 1995.84 8
5 Labs 36 W 16 120 69.12 69.12 3
6 Aux Room 36 W 10 360 129.6 129.6 1