200 HANDBOOK OF ELECTRICAL ENGINEERING


also the IEE Wiring Regulations in its sixteenth form. Such tables cover a wide range of installation
configurations and environmental conditions, not all of which are applicable in the oil industry.
The following tables were compiled to be on similar bases and for installations commonly used in
the oil industry. For example all the reactance data are given for a frequency of 50 Hz. The con-
ductor temperatures are those suitable for the insulation where rated current follows in the cable.
The resistance data of the armouring has been given at a temperature of 80◦C for wire armour-
ing and 60◦C for braided armouring so that the earth loop impedance can be calculated under
fault conditions. The depth of burial of cables is taken to the 0.5 m and the ground temperature
15 ◦C. They should be used as guidance in estimating cable sizes. When calculations are being
finalised for a project then the data from a particular manufacturer should be used. Most of the
data presented were kindly made available by the Anixter Wire and Cable group of companies,
see Reference 6. Reference 4 also provides comprehensive data on many types of cables, and was
used as a source for PVC insulated cables. Reference 7 although somewhat dated is also a valuable
source of data.


Table 9.11. Summary of cable rating and data tables
Table Cable
voltage grade

Brief description

Land based installations:
9.12 600/1000 V PVC insulation
Current ratings of 1-core cables
9.13 600/1000 V PVC insulation
Impedance data in ohms/km
9.14 600/1000 V PVC insulation
Current ratings of 3 & 4-core cables
9.15 600/1000 V XLPE insulation
Current ratings of 1-core cables
9.16 600/1000 V XLPE insulation
Impedance data in ohms/km
9.17 600/1000 V XLPE insulation
Current ratings of 3 & 4-core cables
9.18 3800/6600 V
6350/11,000 V XLPE insulation
8700/15,000 V Current ratings of 1-core cables
9.19 3800/6600 V Impedance data in ohms/km
9.20 6350/11,000 V Impedance data in ohms/km
9.21 8700/15,000 V Impedance data in ohms/km
3800/6600 V
9.22 6350/11,000 V Current ratings of 3-core cables
8700/15,000 V
Marine installations:
9.23 600/1000 V EPR insulation
Current ratings of 1, 3 & 4-core cables
9.24 600/1000 V Impedance data in ohms/km