CABLES, WIRES AND CABLE INSTALLATION PRACTICES 203Table 9.16. Land based Installations. 600/1000 V. Cu/XLPE/PVC/AWA/PVC single core Cu/XLPE/PVC/
SWA/PVC 3 and 4 core
Nominal conductor
area (mm^2 )
Single core
in trefoil3and4
coresApproximate armouring
resistanceResistance
at 90◦C
(ohm/km)Reactance at
50 Hz
(ohm/km)Resistance
at 90◦C
(ohm/km)Reactance
at 50 Hz
(ohm/km)AWA at 80◦C
(ohm/km)
1-coreSWA at 80◦C
(ohm/km)
3/4 core
1.5 15.4 0.103 11.40
2.5 9.45 0.101 9.48
4 5.88 0.0929 5.52
6 3.93 0.0885 4.92
10 2.33 0.0835 4.08
16 1.47 0.0815 2.64
25 0.927 0.0818 2.52
35 0.668 0.0771 2.28
50 0.494 0.104 0.494 0.0765 1.018 1.56
70 0.342 0.101 0.342 0.0754 0.919 1.44
95 0.246 0.0969 0.247 0.0727 0.795 1.176
120 0.196 0.0920 0.197 0.0723 0.559 0.852
150 0.160 0.0945 0.160 0.0728 0.509 0.780
185 0.128 0.0932 0.128 0.0730 0.460 0.708
240 0.0985 0.0902 0.0989 0.0722 0.410 0.624
300 0.0799 0.0883 0.0802 0.0717 0.385 0.564
400 0.0639 0.0886 0.0656 0.0715 0.286 0.408Table 9.17. Land based installations. 600/1000 V. Cu/XLPE/PVC/SWA/PVC 3 and 4 coresNominal conductor
area (mm^2 )
Air Ducts Direct buried Notes1.5 26 26 32
2.5 35 34 42
4474555
6595669
10 82 75 92
16 107 96 119 Thermal resistivity of soil 1.2◦Cm/W
25 140 124 152
35 172 149 182 Ambient air temp. is 25◦C
50 209 177 217 Depth of laying cables is 0.5 m
70 263 218 266
95 324 263 319 Standard ground temp. is 15◦C
120 376 300 363 Conductor surface temp. is 90◦C
150 430 338 406
185 495 382 458
240 584 442 529
300 666 496 592
400 766 570 667Ambient air temperature◦C 2530354045505560
Rating factorKairfor cables laid in air 1.0 0.96 0.92 0.88 0.84 0.79 0.73 0.68
Ground temperature◦C 10152025303540
Rating factorKgrdfor cables laid in the ground 1.03 1.0 0.97 0.93 0.89 0.86 0.82