208 HANDBOOK OF ELECTRICAL ENGINEERING
Table 9.22. Land based Installations. 3800/6600 V. 6350/11,000 V. 8700/15,000 V. Cu/XLPE/PVC/SWA/
PVC three cores
Nominal conductor
area (mm^2 )
Air Ducts Direct
buried
Notes
25 145 125 140 Thermal resistivity of soil is 1.2◦Cm/W
35 175 150 170
50 220 180 210 Ambient air temp. is 25◦C.
70 270 215 255 Depth of laying cables is 0.5 m
95 330 255 300
120 375 290 340 Standard ground temp. is 15◦C
150 430 330 380
185 490 370 430 Conductor surface temp. is 90◦C.
240 570 425 490
300 650 470 540
400 740 530 600
Ambient air temperature◦C 2530354045505560
Rating factorKairfor cables laid in air 1.0 0.96 0.92 0.88 0.84 0.79 0.73 0.68
Ground temperature◦C 10152025303540
Rating factorKgrdfor cables laid in the ground 1.03 1.0 0.97 0.93 0.89 0.86 0.82
Table 9.23. Marine and offshore 600/1000 V Cu/EPR/CSP/GSWB or PBWB/CSP or PVC
installations. Cables run on open trays or enclosed in air. 1 to 6×single, 3 or 4 cores
Nominal conductor
area (mm^2 )
Single
cores
3and4
cores
Notes
1.0 17 12 Ambient air temperature is 45◦C
1.5 21 15
2.5 30 21
4 40 29 Conductor surface temperature is 90◦C.
65136
10 71 50
16 95 67
25 125 89
35 155 105
50 190 135
70 240 170
95 290 205
120 340 240
150 385 270
185 440 305
240 520 365
300 590 415
400 670 470
Ambient air tem- 35 40 45 50 55 60 65 70 75 80
perature◦C
Rating factor for 1.11 1.05 1.0 0.94 0.88 0.82 0.75 0.69 0.58 0.47
cables laid in air