276 HANDBOOK OF ELECTRICAL ENGINEERING
11.5.2 Calculation of fault current – rms symmetrical values
From sub-section 11.5.1 the emfE(E′′,E′orE) and appropriate reactanceX(Xd′′,X′dorXsd)are
known. Hence the symmetrical fault currentIfmay be easily calculated:
If=
E
X
per unit
For example:
A 6600 V, 4.13 MVA generator hasX′′d= 15 .5%,X′d= 23 .5% andXsd=205%
At full load with a power factor of 0.8 lagging the corresponding emfs are therefore:
E′′= 1 .1pu,E′= 1 .156 pu and E = 2 .77 pu
The rms fault currents are therefore:
If′′=
1. 1
0. 155
= 7 .097 pu (2564 amps)
If′ =
1. 156
0235
= 4 .919 pu (1776 amps)
If=
2. 77
2. 05
= 1 .351 pu (488 amps)
A typical oil industry power system can be approximated as shown in Figure 11.6. The major-
ity of oil industry systems are of the radial distribution type, with feeders radiating away from a
Figure 11.6 One-line diagram of an equivalent power system that has its own dedicated generators.