428 HANDBOOK OF ELECTRICAL ENGINEERING
Figure 15.12 Instantaneous voltages and currents in an induction motor supplied from a voltage source inverter.
Table 15.5. Peak values of har-
monic current components
Harmonic
number
Peak value and sign
of the component
current
1 +554.74
5 −110.95
7 −79.25
11 +50.43
13 +42.67
17 −32.63
19 −29.20
From the Worked Example 15.4.3.1 the combined impedance of the rotor and magnetising
branches isZm 2 = 0. 00348 +j 0 .5362 ohms. Adding the stator impedance gives,
Z 1 m 2 = 0. 00878 +j 0 .7711 ohms
All the harmonics of the supply current have either zero or 180◦phase shift as seen in Table 15.5.
The fifth harmonic supply currentI 15 is− 110. 95 /
√
2 amps (rms). Inject this current into the circuit.