576 HANDBOOK OF ELECTRICAL ENGINEERING
Hence the terminal voltage of the generatorVgnis:-Vgn=EoZogn
Zgn
= 0. 9691 −j 0 .0359 pu, which has a magnitude of 0.9697 pu.t) Starting conditionsThe motor starter is closed. Repeat the procedure as for s) but use the motor starting impedance,
and using the suffix ‘s’ for starting.The parallel impedance of the running motor isZmn:-Rms= 3 .8244 andXms=j 0 .9875 puThe total load resistance on the SWBD isRlswhere:-Rls=Ro×Rms
Ro+Rms= 1 .4095 puThe total load reactance on the SWBD isXlswhere:-Xls=Xo×Xms
Xo+Xms= 0 .7991 puThe series equivalent resistance isRogs:-Rogs=0. 7991 × 0. 7991 × 1. 4095
0. 79912 + 1. 40952
= 0 .3429 puThe series equivalent reactance isXogs:-Xogs=0. 7991 × 1. 4095 × 1. 4095
0. 79912 + 1. 40952
= 0 .6047 puThe total impedance seen by the generator emfEoisZgs:-Zgs=Rg+Rogs+j(Xg+Xogs)
= 0. 02 + 0. 3429 +j( 0. 25 + 0. 6047 )
= 0. 3629 +j 0 .8547 puThe current in the generatorIgsis:-Igns=Eo=( 1. 0686 −j 0. 1072 )( 0. 3629 −j 0. 8547 )
0. 8622
= 0. 5560 −j 1 .0142 pu