578 HANDBOOK OF ELECTRICAL ENGINEERING
All the impedances are in their complex formR+jX.
The simplifications made in t) have been applied viz:-
- Cable impedances have been ignored.
- Transformer impedances have been ignored.
- All the standing loads are grouped at the generator terminals.
The initial conditions are easily calculated. The terminal voltageVois known and assumed
to be 1. 0 +j 0 .0 per unit. The motor starter is open. The initial circuit consists ofZlin series
withZgand is fed byEo. The initial load currentIlisIlo.
Ilo=
Vo
Zl
andEo=Vo+Ilo
Therefore it consists ofZlin series withZgand is fed byEo. The initial load currentIlisIlo.
Eo=Vo
(
1 +
Vo
Zl
)
The general case for the running conditions are also easily calculated. The motor starter
is closed. The motor and load impedance are then connected in parallel. The total of these
impedances isZlmin series withZgand is fed byEo. The initial load currentIlwhere:-
Zlm=
ZlZm
Zl+Zm
and
V=
EoZlm
Zlm+Zg
=
Vo( 1 +Zg)Zlm
Zl(Zlm+Zg)
Let
a=(Zl+Zg)Zlm
and
b=(Zlm+Zg)Zl
Therefore
V=
aVo
b
The Percentage volt-dropV=
(
Vo−V
V
)
×100%
V=
(
Vo−
aVo
b