Simulink Control Design™ - MathWorks

(Tuis.) #1

  • Stabilize closed loop system


By default, the tuning goal imposes a stability requirement on the closed-loop transfer
function from the specified inputs to outputs, in addition to the gain constraint. If
stability is not required or cannot be achieved, select No to remove the stability
requirement. For example, if the gain constraint applies to an unstable open-loop
transfer function, select No.


  • Equalize loop interactions


For multi-loop or MIMO loop gain constraints, the feedback channels are automatically
rescaled to equalize the off-diagonal (loop interaction) terms in the open-loop transfer
function. Select Off to disable such scaling and shape the unscaled open-loop
response.


  • Apply goal to


Use this option when tuning multiple models at once, such as an array of models
obtained by linearizing a Simulink model at different operating points or block-
parameter values. By default, active tuning goals are enforced for all models. To
enforce a tuning requirement for a subset of models in an array, select Only Models.
Then, enter the array indices of the models for which the goal is enforced. For
example, suppose you want to apply the tuning goal to the second, third, and fourth
models in a model array. To restrict enforcement of the requirement, enter 2:4 in the
Only Models text box.

For more information about tuning for multiple models, see “Robust Tuning
Approaches” (Robust Control Toolbox).

Algorithms


Evaluating Tuning Goals

When you tune a control system, the software converts each tuning goal into a normalized
scalar value f(x). Here, x is the vector of free (tunable) parameters in the control system.
The software then adjusts the parameter values to minimize f(x) or to drive f(x) below 1 if
the tuning goal is a hard constraint.

For Maximum Loop Gain Goal, f(x) is given by:

fx = WTD−^1 TD

.


10 Control System Tuning

Free download pdf