output of the controller at steady-state is 0.5. To remain within these limits, specify a sine
amplitude of 0.1. Specifying a scalar value uses the same amplitude at all four
frequencies.

For an asymptotically stable plant, the tuner also injects a step signal to estimate the
plant DC gain. Choose an amplitude for this step signal based on the same considerations
you used to choose the sine amplitudes. For this example, enter 0.1 in the Step
Amplitude field as well.

Specify Design Goals

Finally, specify the target bandwidth for tuning. As noted previously, the target bandwidth
is 8000 radians per second. Enter 8000 in the Bandwidth field. The default target phase
margin, 60 degrees, corresponds to an overshoot of about 10% or better.

Tune the PID Controller and Validate the Results

Click Tune to begin the two simulations of the buck converter and tune the PID
Controller.

At the conclusion of the tuning procedure the tuned gains, estimated phase margin and
nominal plant input are displayed in Frequency Response Based PID Tuner dialog in
the Tuning Results section. Check the estimated phase margin to ensure that it is close
to the Target phase margin.