Section 8 - Wall Surfacing (Page 29 of 32)


EXECUTION
INSTALLATION RULES (continued)

DESCRIPTION E C P



6.1


G E N E R A L


GENERAL (continued)


6.1.12 Paneling JOINTS shall be:
6.1.12.1 Smooth and flush to create a homogenous look.
6.1.12.2 Plumb within 1/16" (1.6 mm) in 96" (2438 mm).
6.1.13 BACKS of wood paneling shall be sealed with at least two coats of sealer.
6.1.14 FLATNESS of installed and removable sheet products (see Test E illustrations in COMPLIANCE) shall not
exceed:
6.1.14.1 0.050" (1.3 mm) per 12" (305 mm) or portion thereof. M
6.1.14.2 0.036" (0.9 mm) per 12" (305 mm) or portion thereof. M
6.1.14.3 0.027" (0.7 mm) per 12" (305 mm) or portion thereof. M

6.1.15 EQUIPMENT CUTOUTS shall be neatly cut out by the installer, provided the templates are
furnished in a timely manner.

MM

6.1.16 HARDWARE shall be:
6.1.16.1 Installed neatly without tear-out of surrounding stock.
6.1.16.2 Installed per the manufacturer's instructions.
6.1.16.3 Installed using all furnished fasteners and fastener's provisions
6.1.16.4 Adjusted for smooth operation.
6.1.17 AREAS of installation shall be left broom clean.
6.1.17.1 Debris shall be removed and dumped in containers provided by the contractor.
6.1.17.2 Items installed shall be cleaned of pencil or ink marks.
6.1.18 Entire installation shall present FIRST-CLASS WORKMANSHIP in compliance with these standards.

6.2


P R O D U C T S P E C I F I C 


6.2.1


V E N E E R


At VENEERED wall surfacing:

6.2.1.1


For TRANSPARENT FINISH, the installer shall pay special attention to the COLOR and the
GRAIN of the various panels and trim pieces to ensure they are installed in compliance with the
GRADE specified.
6.2.1.2 PANELS shall be installed as specified by the architect.
6.2.1.3 GLUING with construction adhesive is permitted.
6.2.1.4 A maximum of 3/4" (19 mm) REVEAL at the ceiling to facilitate concealed fasteners is acceptable.
6.2.1.5 EDGES of core that are not self-edged shall have one coat sealer applied before installation.
6.2.2 At DECORATIVE LAMINATE wall surfacing:
6.2.2.1 EXPOSED FASTENING is not permitted, except:
6.2.2.1.1 At removable panels.
6.2.2.2 PANELS shall be installed as specified.
6.2.2.3 GLUING with construction adhesive is permitted.
6.2.2.4 A maximum of 3/4" (19 mm) REVEAL at the ceiling to facilitate concealed fasteners is acceptable.
6.2.2.5 EDGES of core that are not self-edged shall have one coat sealer applied before installation.
6.2.2.6 SCRATCHES and CHIP-OUT shall be inconspicuous beyond:
6.2.2.6.1 72" (1830 mm) M
6.2.2.6.2 48" (1220 mm) M
6.2.2.6.3 24" (610 mm) M