CASEWORK INTEGRITY
(Page 5 of 5)

TABLE TEST UNIT - Shall be 48" (1219 mm) long, 24" (610 mm) deep, and 36" (914 mm) high. A top of 1"-(25.4 mm) thick medium-
density fiberboard shall be positioned on the table so that it will overhang the frame perimeter by 1" (25.4 mm), and its weight shall
be included in the test as live load. Tables are represented by a large range of styles and designs, including free-standing tables,
desks, aprons mounted between two fixed areas (such as a wall or casework), mobile tables (free-standing tables on wheels or
casters), and mobile under-counter units.

TABLE STRUCTURAL INTEGRITY TEST


CHALLENGES the table components to a normal load.

PROCEDURE - Load the table top with an evenly distributed load of no less than 300 lbs
(136 kg) for mobile, 600 lbs (272 kg) for free-standing, and 2000 lbs (907 kg) for fixed.
Include the weight of the working surface as a live load by using solid steel bars, each
weighing 50 lbs (22.7 kg).

ACCEPTANCE LEVEL - No structural breakage shall occur, and the apron rails shall not
deflect more than 1/8" (3.2 mm). In the case of a table with a drawer, the deflection of the rail
shall not interfere with the function of the drawer.