417
Appendix B
© 2009, AWI, AWMAC, WI - Architectural Woodwork Standards - 1st Edition, October 1, 2009
(Appendix B is not part of the AWS for compliance purposes)
C. All work abutting other building components shall be properly scribed.
D. Mechanical fasteners used at exposed and semi-exposed surfaces, excluding installation attachment screws and those
securing cabinets end to end, shall be countersunk.
E. Equipment cutouts shown on plans shall be cut by the installer.
3.03. ADJUSTING & TOUCH UP
A. Before completion of the installation, the installer shall adjust all moving and operating parts to function smoothly and
correctly.
B. All nicks, chips, and scratches in the finish shall be filled and retouched. Damaged items that cannot be repaired shall be
replaced.
3.04. CLEANUP
A. Upon completion of installation, the installer shall clean all installed items of pencil and ink marks and broom clean the
area of operation, depositing debris in containers provided by the general contractor.
END OF SECTION
CSI Section 06 41 00
Wood and Plastic Laminate Casework
B