Transmission Techniques: Wire and Cable 441

14.28.5 Plenum Cable

Plenum cable is used in ceilings where the air handling
system uses the plenum as the delivery or the return air
duct. Because of its flame-resistant and low
smoke-emission properties, the special compound used
in plenum cable jackets and insulations has been
accepted under the provisions of the NEC and classified
by Underwriters Laboratories Inc. (UL) for use without
conduit in air plenums.
In a typical modern commercial building, cables are
installed in the enclosed space between drop ceilings
and the floors from which they are suspended. This area
is also frequently used as a return air plenum for a
building’s heating and cooling system. Because these
air ducts often run across an entire story unobstructed,

Figure 14-23. National Electrical Code substitution and hierarchy. Courtesy Belden.

Article
800

Article
725

Article
760

Article
820

Plenum

Riser

General
Purpose

Dwellings

CATVP

CATVR

CATV

CATVX CMX

MPG
MP
CMG
CM

MPR
CMR

MPP
CMP CL3P

CL2P

PLTC

CL2R

CL3

CL2

CL3X

CL2X

CL3R

FPL

FPLR

FPLP

MPP, MPR, MPG, MP—Multipurpose Cables
CMP, CMR, CMG, CM, CMX—Communications Cables
CL3P, CL3R, CL3, CL3X, CL2P, CL2R, CL2, CL2X—Class 2 and Class 3 Remote-Control, Signaling and Power Limited Cables
FPLP, FPLR, FPL—Power Limited Fire Alarm Cables
CATVP, CATVR, CATV, CATVX—Community Antenna Television and Radio Distribution Cables
OFNP, OFNR, OFNG, OFN—Nonconductive Optical Fiber Cables
OFCP, OFCR, OFCG, OFC—Conductive Optical Fiber Cables
PLTC—Power Limited Tray Cables

Article
770

OFNP OFCP

OFNR OFCR

OFNG OFCC

Non-
conductive Conductive

Figure 14-24. Canadian Electrical Code cable substitution
hierarchy per C22.2 #214—Communication Cables.


CMP
FT6

CMR
UL1666 — Riser

CMG
FT4

CM
UL Vertical Tray

CMX
UL VW1

CMH
CSA FT1

The following cable substitutions
may be used:
Communication cables marked
MPP, CMP, MPR, CMR, MPG,
CMG, MP, CM, CMX, CMH, FT6,
and FT4 have been found to meet
the standard criteria for FT1.
Communication cables marked
MPP, CMP, MPR, CMR, MPG,
CMG, and FT6 have been found to
meet the standard criteria for FT4.
Communication cables marked MPP
and CMP have been found to meet
the standard criteria for FT6.