Transmission Techniques: Wire and Cable 441
14.28.5 Plenum Cable
Plenum cable is used in ceilings where the air handling
system uses the plenum as the delivery or the return air
duct. Because of its flame-resistant and low
smoke-emission properties, the special compound used
in plenum cable jackets and insulations has been
accepted under the provisions of the NEC and classified
by Underwriters Laboratories Inc. (UL) for use without
conduit in air plenums.
In a typical modern commercial building, cables are
installed in the enclosed space between drop ceilings
and the floors from which they are suspended. This area
is also frequently used as a return air plenum for a
building’s heating and cooling system. Because these
air ducts often run across an entire story unobstructed,
Figure 14-23. National Electrical Code substitution and hierarchy. Courtesy Belden.
Article
800
Article
725
Article
760
Article
820
Plenum
Riser
General
Purpose
Dwellings
CATVP
CATVR
CATV
CATVX CMX
MPG
MP
CMG
CM
MPR
CMR
MPP
CMP CL3P
CL2P
PLTC
CL2R
CL3
CL2
CL3X
CL2X
CL3R
FPL
FPLR
FPLP
MPP, MPR, MPG, MP—Multipurpose Cables
CMP, CMR, CMG, CM, CMX—Communications Cables
CL3P, CL3R, CL3, CL3X, CL2P, CL2R, CL2, CL2X—Class 2 and Class 3 Remote-Control, Signaling and Power Limited Cables
FPLP, FPLR, FPL—Power Limited Fire Alarm Cables
CATVP, CATVR, CATV, CATVX—Community Antenna Television and Radio Distribution Cables
OFNP, OFNR, OFNG, OFN—Nonconductive Optical Fiber Cables
OFCP, OFCR, OFCG, OFC—Conductive Optical Fiber Cables
PLTC—Power Limited Tray Cables
Article
770
OFNP OFCP
OFNR OFCR
OFNG OFCC
Non-
conductive Conductive
Figure 14-24. Canadian Electrical Code cable substitution
hierarchy per C22.2 #214—Communication Cables.
CMP
FT6
CMR
UL1666 — Riser
CMG
FT4
CM
UL Vertical Tray
CMX
UL VW1
CMH
CSA FT1
The following cable substitutions
may be used:
Communication cables marked
MPP, CMP, MPR, CMR, MPG,
CMG, MP, CM, CMX, CMH, FT6,
and FT4 have been found to meet
the standard criteria for FT1.
Communication cables marked
MPP, CMP, MPR, CMR, MPG,
CMG, and FT6 have been found to
meet the standard criteria for FT4.
Communication cables marked MPP
and CMP have been found to meet
the standard criteria for FT6.