Transmission Techniques: Wire and Cable 44114.28.5 Plenum CablePlenum cable is used in ceilings where the air handling
system uses the plenum as the delivery or the return air
duct. Because of its flame-resistant and low
smoke-emission properties, the special compound used
in plenum cable jackets and insulations has been
accepted under the provisions of the NEC and classified
by Underwriters Laboratories Inc. (UL) for use without
conduit in air plenums.
In a typical modern commercial building, cables are
installed in the enclosed space between drop ceilings
and the floors from which they are suspended. This area
is also frequently used as a return air plenum for a
building’s heating and cooling system. Because these
air ducts often run across an entire story unobstructed,Figure 14-23. National Electrical Code substitution and hierarchy. Courtesy Belden.Article
800Article
725Article
760Article
820PlenumRiserGeneral
PurposeDwellingsCATVPCATVRCATVCATVX CMXMPG
MP
CMG
CMMPR
CMRMPP
CMP CL3PCL2PPLTCCL2RCL3CL2CL3XCL2XCL3RFPLFPLRFPLPMPP, MPR, MPG, MP—Multipurpose Cables
CMP, CMR, CMG, CM, CMX—Communications Cables
CL3P, CL3R, CL3, CL3X, CL2P, CL2R, CL2, CL2X—Class 2 and Class 3 Remote-Control, Signaling and Power Limited Cables
FPLP, FPLR, FPL—Power Limited Fire Alarm Cables
CATVP, CATVR, CATV, CATVX—Community Antenna Television and Radio Distribution Cables
OFNP, OFNR, OFNG, OFN—Nonconductive Optical Fiber Cables
OFCP, OFCR, OFCG, OFC—Conductive Optical Fiber Cables
PLTC—Power Limited Tray CablesArticle
770OFNP OFCPOFNR OFCROFNG OFCCNon-
conductive ConductiveFigure 14-24. Canadian Electrical Code cable substitution
hierarchy per C22.2 #214—Communication Cables.
CMP
FT6CMR
UL1666 — RiserCMG
FT4CM
UL Vertical TrayCMX
UL VW1CMH
CSA FT1The following cable substitutions
may be used:
Communication cables marked
MPP, CMP, MPR, CMR, MPG,
CMG, MP, CM, CMX, CMH, FT6,
and FT4 have been found to meet
the standard criteria for FT1.
Communication cables marked
MPP, CMP, MPR, CMR, MPG,
CMG, and FT6 have been found to
meet the standard criteria for FT4.
Communication cables marked MPP
and CMP have been found to meet
the standard criteria for FT6.