Handbook for Sound Engineers

(Wang) #1

442 Chapter 14


they can be an invitation to disaster if fire breaks out.
Heat, flames, and smoke can spread rapidly throughout
the air duct system and building if the fire is able to feed
on combustible materials (such as cable insulations) in
the plenum. To eliminate this problem and to keep
fumes from entering the air handling system, the NEC
requires that conventional cables always be installed in
metal conduit when used in plenums.


Plenums, with their draft and openness between
different areas, cause fire and smoke to spread, so the
1975 NEC prohibited the use of electrical cables in
plenums and ducts unless cables were installed in metal
conduit. In 1978, Sections 725-2(b) (signaling cables),
760-4(d) (fire-protection cable), and 800-3(d) (commu-
nication/telephone cables) of the NEC allowed that
cables “listed as having adequate fire-resistance and
low-smoke producing characteristics shall be permitted
for ducts, hollow spaces used as ducts, and plenums
other than those described in Section 300-22(a).”


While plenum cable costs more than conventional
cable, the overall installed cost is dramatically lower
because it eliminates the added cost of conduit along
with the increased time and labor required to install it.


In 1981 the jacket and insulation compound used in
plenum cables was tested and found acceptable under
the terms of the NEC and was classified by UL for use
without conduit in air return ducts and plenums. Fig.
14-25 shows the UL standard 910 plenum flame test
using a modified Steiner tunnel equipped with a special
rack to hold test cables.


Virtually any cable can be made in a plenum version.
The practical limit is the amount of flammable material


in the cable and its ability to pass the Steiner Tunnel Test,
shown in Fig. 14-25. Originally plenum cable was all
Teflon inside and out. Today most plenum cables have a
Teflon core with a special PVC jacket which meets the
fire rating. But there are a number of compounds such as
Halar® and Solef® that can also be used.

14.28.6 Power Distribution Safety

Electricity kills! No matter how confident we are we
must always be careful around electricity. Fibrillation is
a nasty and relatively slow death so it is important that
Defibrillators are accessible when working around elec-
tricity. Table 14-37 displays the small amounts of current
that is required to hurt or kill a person.

14.28.6.1 Ground-Fault Interrupters

Ground-fault circuit interrupters (GFCIs) are sometimes
called earth leakage or residual-current circuit breakers.
GFCIs sense leakage current to earth ground from the
hot or neutral leg and interrupt the circuit automatically
within 25 ms if the current exceeds 4 to 6 ma. These val-
ues are determined to be the maximum safe levels before
a human heart goes into ventricular fibrillation. GFCIs
do not work when current passes from one line to the
other line through a person, for instance. They do not
work as a circuit breaker.
One type of GFCI is the core-balance protection
device, Fig. 14-26. The hot and neutral power conduc-

Figure 14-25. Plenum cable flame test, UL standard 910.

Air
duct

Fire
alarm

Air
return

Sound
system

Suspended
ceiling

Structural
support

Floor

Differential
manometer 6 × 6 window–door Removable top
panel

Air supply
250 ft/min
Cable
and tray

Fire
end

Adjustable
shutter

Gas supply for igniting
25 ft length of test sample

Light
To draft source
chamber

Vents for
gas
analysis

PhotoSheet
metal vent
pipe electric
cell

Sheet
metal
vent
pipe

Vent
end

Thermocouples

Ceiling air plenum area

19 windows 2¾ ×11¾
Free download pdf