CHAPTER 9
207
BUILDING AND
STRUCTURES
FORMULAS
LOAD-AND-RESISTANCE FACTOR
DESIGN FOR SHEAR IN BUILDINGS
Based on the American Institute of Steel Construction(AISC)specifications for
load-and-resistance factor design(LRFD) for buildings, the shear capacity Vu,
kip (kN4.448kip), of flexural members may be computed from the fol-
lowing:
(9.1)
(9.2)
(9.3)
whereFywspecified minimum yield stress of web, ksi(MPa6.894ksi)
Awweb area, in^2 (mm^2 )dtw
k5 if a/hexceeds 3.0 or 67,600/(h/tw)^2 , or if stiffeners are not required
5 5/(a/h)^2 , otherwise
Stiffeners are required when the shear exceeds Vu. In unstiffened girders,
h/twmay not exceed 260. In girders with stiffeners, maximum h/twpermitted is
for or for ,whereFyf
is the specified minimum yield stress, ksi, of the flange. For shear capacity with
tension-field action, see the AISC specification for LRFD.
2,000/Fyf a/h1.5 14,000/Fyf (Fyf16.5) a/h > 1.5
1872 k/Fyw
Vu
23,760kAw
(h/tw)^2
when
h
tw
1.25
Vu
0.54FywAw
h/tw
when
h
tw
1.25
Vu0.54FywAw when
h
tw