Modern Control Engineering

(Chris Devlin) #1
Section 6–6 / Lead Compensation 313

2.By drawing the root-locus plot of the uncompensated system (original system),


ascertain whether or not the gain adjustment alone can yield the desired closed-


loop poles. If not, calculate the angle deficiency f. This angle must be contributed


by the lead compensator if the new root locus is to pass through the desired loca-


tions for the dominant closed-loop poles.


3.Assume the lead compensator Gc(s)to be


whereaandTare determined from the angle deficiency.Kcis determined from


the requirement of the open-loop gain.


4.If static error constants are not specified, determine the location of the pole and


zero of the lead compensator so that the lead compensator will contribute the nec-


essary angle f. If no other requirements are imposed on the system, try to make


the value of aas large as possible. A larger value of agenerally results in a larger


value of Kv,which is desirable. Note that


5.Determine the value of Kc of the lead compensator from the magnitude condition.


Once a compensator has been designed, check to see whether all performance spec-


ifications have been met. If the compensated system does not meet the performance


specifications, then repeat the design procedure by adjusting the compensator pole and


zero until all such specifications are met. If a large static error constant is required, cas-


cade a lag network or alter the lead compensator to a lag–lead compensator.


Note that if the selected dominant closed-loop poles are not really dominant, or if


the selected dominant closed-loop poles do not yield the desired result, it will be nec-


essary to modify the location of the pair of such selected dominant closed-loop poles.


(The closed-loop poles other than dominant ones modify the response obtained from the


dominant closed-loop poles alone. The amount of modification depends on the location


of these remaining closed-loop poles.) Also, the closed-loop zeros affect the response if


they are located near the origin.


EXAMPLE 6–6 Consider the position control system shown in Figure 6–39(a). The feedforward transfer


function is

The root-locus plot for this system is shown in Figure 6–39(b). The closed-loop transfer function
for the system is

=

10

(s+0.5+j3.1225)(s+0.5-j3.1225)

C(s)
R(s)

=

10

s^2 +s+ 10

G(s)=

10

s(s+ 1 )

Kv=limsS 0 sGc(s)G(s)=Kca limsS 0 sGc(s)

Gc(s)=Kc a


Ts+ 1


aTs+ 1


=Kc


s+


1


T


s+


1


aT


, (0 6 a 6 1)

Free download pdf