340 Chapter 6 / Control Systems Analysis and Design by the Root-Locus Method0jvsB AP55 °j 5j 4j 3j 2j 1- j 4
- j 3
- j 2
- j 1
- 10 – 9 – 8 – 7 – 6 – 5 – 4 – 3 – 2 – 112
Figure 6–58
Determination of the
desired pole-zero
location.By simple calculations, we find that if we choose , thenand if we choose , thenSince is one of the time constants of the lag–lead compensator, it should not be too large. If
can be acceptable from practical viewpoint, then we may choose. ThenThus, the lag–lead compensator becomesThe compensated system will have the open-loop transfer functionNo cancellation occurs in this case, and the compensated system is of fourth order. Because the
angle contribution of the phase lag portion of the lag–lead network is quite small, the dominant
closed-loop poles are located very near the desired location. In fact, the location of the dominant
closed-loop poles can be found from the characteristic equation as follows: The characteristic
equation of the compensated system iswhich can be simplified to=(s+2.4539+j4.3099)(s+2.4539-j4.3099)(s+0.1003)(s+3.8604)= 0s^4 +8.8685s^3 +44.4219s^2 +99.3188s+9.52(s+8.34)(s+0.0285)s(s+0.5)+ 40 (s+2.38)(s+0.1)= 0Gc(s)G(s)=40(s+2.38)(s+0.1)
(s+8.34)(s+0.0285)s(s+0.5)Gc(s)=(10)as+2.38
s+8.34bas+0.1
s+0.0285b1
bT 2=
1
3.503* 10
=0.0285
T 2 = 10 T 2 = 10
T 2
17 magnitude 7 0.99, - 1 ° 6 angle 60 °T 2 = 10
17 magnitude 7 0.98, -1.5° 6 angle 60 °T 2 = 5
Openmirrors.com