Section 8–7 / Zero-Placement Approach to Improve Response Characteristics 599we have
(8–6)
The two controllers Gc1andGc2can be determined from Equations (8–5) and (8–6).
EXAMPLE 8–4 Consider the two-degrees-of-freedom control system shown in Figure 8–33. The plant transfer
function is given byDesign controllers and such that the maximum overshoot in the response to the
unit-step reference input be less than 19%, but more than 2%, and the settling time be less than
1 sec. It is desired that the steady-state errors in following the ramp reference input and acceler-
ation reference input be zero. The response to the unit-step disturbance input should have a small
amplitude and settle to zero quickly.
To design suitable controllers and first note thatTo simplify the notation, let us defineGc=Gc1+Gc2Then=
10
s(s+1)+10GcY(s)
D(s)=
Gp
1 +Gp Gc=
10
s(s+1)1 +10
s(s+1)GcY(s)
D(s)=
Gp
1 +GpAGc1+Gc2BGc1(s) Gc2(s),Gc1(s) Gc2(s)Gp(s)=10
s(s+1)Gp(s)=
AKa-a 1 Bs+AKb-a 0 B+AKg-a 2 Bs^2
Ks
1
A(s)
Gc2= c
as+b+gs^2
s
-
a 1 s+a 0 +a 2 s^2
Ks
d
1
A(s)
Gc 1 (s) Gp(s)R(s) U(s) Y(s)D(s)Gc 2 (s)++
++Figure 8–33
Two-degrees-
of-freedom control
system.