In applying Carson’s equations for both concentric neutral and tape shielded cables, the numbering
of conductors and neutrals is important. For example, a three-phase underground circuit with an
additional neutral conductor must be numbered as
1 ¼phase conductor #1
2 ¼phase conductor #2
3 ¼phase conductor #3
4 ¼neutral of conductor #1
5 ¼neutral of conductor #2
6 ¼neutral of conductor #3
7 ¼additional neutral conductor (if present)
Example 21.3
A single-phase circuit consists of a 1=0 AA tape shielded cable and a 1=0 CU neutral conductor as shown
in Fig. 21.10.
Cable Data: 1=0AA
Inside diameter of tape shield¼ds¼1.084 in.
Resistance¼0.97V=mile
GMRp¼0.0111 ft
Tape shield thickness¼T¼8 mils
Neutral Data: 1=0 Copper, 7 strand
Resistance¼0.607V=mile
GMRn¼0.01113 ft
Distance between cable and neutral¼Dnm¼3 in.
The resistance of the tape shield is computed according to Eq. (21.41):
rshield¼
18 : 826
dsT
¼
18 : 826
1 : 084 8
¼ 2 : 1705 V=mile
The GMR of the tape shield is computed according toEq. (21.42):
GMRshield¼
ds
2
T
2000
12
¼
1 : 084
2
8
2000
12
¼ 0 :0455 ft
Using the relations defined in Eqs. (21.43) through (21.45) and Carson’s equations results in a 3 3
primitive impedance matrix:
zprimitive¼
1 : 0653 þj 1 :5088 0: 0953 þj 1 :3377 0: 0953 þ 1 : 1309
0 : 0953 þj 1 :3377 2: 2658 þj 1 :3377 0: 0953 þj 1 : 1309
0 : 0953 þj 1 :1309 0: 0953 þj 1 :1309 0: 7023 þj 1 : 5085
2
4
3
(^5) V=mile
Applying Kron’s reduction method will result in a single impedance that
represents the equivalent single-phase impedance of the tape shield cable and
the neutral conductor.
zlp¼ 1 : 3368 þj 0 : 6028 V=mile
3 0
FIGURE 21.10 Single-
phase tape shield with
neutral.