Electric Power Generation, Transmission, and Distribution

(Tina Meador) #1

21.1.4.7 Closed Delta Connected Regulators


Three single-phase regulators can be connected in a closed delta as shown in Fig. 21.19. In the figure, the
regulators are shown in the raise position. The closed delta connection is typically used in three-wire
delta feeders. Note that the potential transformers for this connection are monitoring the load side line-
to-line voltages and the current transformers are monitoring the load side line currents.
Applying the basic voltage and current Eqs. (21.77) through (21.83) of the regulator in the raise
position, the following voltage and current relations are derived for the closed delta connection.


VAB
VBC
VCA

2
4

3

(^5) ¼
aRab 1 aRbc 0
0 aRbc 1 aRca
1 aRab 0 aRca
2
4
3
5
Vab
Vbc
Vca
2
4
3
(^5) (21:103)
Equation (21.101) in abbreviated form can be written as
½Š¼VLLABC ½ŠaRVDabc½ŠVLLabc (21:104)
When the load side voltages are known, the source side voltages can be determined by
½Š¼VLLabc ½ŠaRVDABC½ŠVLLABC (21:105)
where
½Š¼aRVDABC ½ŠaRVDabc^1 (21:106)
In a similar manner, the relationships between the load side and source side line currents are given by
Ia
Ib
Ic
2
4
3
(^5) ¼
aRab 01 aRca
1 aRab aRbc 0
01 aRbc aRca
2
4
3
5
IA
IB
IC
2
4
3
(^5) (21:107)
A
a
S
L
C
B
IA
IA
IC
Ibc IB
IB
IC
Ic
Ia
Ib I
b
b
Ic c
Ica
Iab
Ia
SL
L
S
L
SL S
SL
FIGURE 21.19 Delta connected type B regulators.