Electric Power Generation, Transmission, and Distribution

(Tina Meador) #1

6.7.2.3 Medium-Voltage SF6 Circuit Breakers


SF6 circuit breakers have the same advantages as vacuum circuit breakers but there is some environ-
mental concern with the SF6 gas.


6.7.3 Low-Voltage Switchgear


Low voltage is 600 V and below. The most common voltage used is 480 V.


6.7.3.1 Low-Voltage Air Circuit Breakers


Air circuit breakers are used in load centers that may include a power transformer. Air circuit breakers
are used for motors greater than 200 hp and less than about 600 hp. Low-voltage circuit breakers are self-
contained in that fault protection is an integral part of the breaker. Low-voltage devices, which do not
contain fault protection devices, are referred to as low-voltage switches. Low-voltage breakers may be
obtained with various combinations of trip elements. Long time, short time, and ground trip elements
may be obtained in various combinations.
Low-voltage breakers manufactured before 1970 will contain oil dashpot time delay trip elements.
Breakers manufactured after the mid-1970s until about 1990 will contain solid-state analog trip
elements. Breakers manufactured after 1990 will contain digital trip elements. The digital elements
provide much more flexibility.
A circuit that may be large enough for a load center circuit breaker but is operated several times a day
should not be put on a load center circuit breaker. The circuit breaker would be put through its useful
life in a very short time. A motor starter would be a better choice.


6.7.4 Motor Control Centers


Motor control centers are self-contained and may include molded case breakers or combination starters.
Molded case breakers are available as either magnetic or thermal-magnetic. The magnetic trip breakers
are instantaneous trip only and the thermal-magnetic trip breakers are time delay with instantaneous
trip. Magnetic breakers can be used with a contactor to make a combination starter. Time delay trip is
provided by overload relays mounted on the contactor. Solid-state equipment is available to use in
motor control centers and allows much greater flexibility.


6.7.5 Circuit Interruption


The purpose of a circuit breaker is to provide a method of interrupting the circuit either to turn the load
on and off or to interrupt fault current. The first requirement is based on the full load current of the
load. The second requirement is based on the maximum fault current as determined by the fault current
study. There is no relationship between the load current and the fault current. If modifications are made
to the electric power system, the fault interrupting current requirement may increase. Failure to
recognize this could result in the catastrophic failure of a breaker.


6.8 Auxiliary Transformers


6.8.1 Selection of Percent Impedance


The transformer impedance is always compromised. High transformer impedance will limit fault
current and reduce the required interrupting capability of switchgear and, therefore, reduce the cost.
Low impedance will reduce the voltage drop through the transformer and therefore improve voltage
regulation. A careful analysis using a load flow study will help in arriving at the best compromise.

Free download pdf