Annunciator cable shall be #18awg solid Black (-) and White (+) and
twisted shield with Blue tape around each end of the cable when made up in
a junction box, cable types listed below or equal approved by
SimplexGrinnell.
24 volt Device power and 24 volt annunciator power shall be #12awg
solid THHN one Black (-) and one Red (+). Wire size may be reduced to
#14awg Solid THHN with approval of SimplexGrinnell.
Speaker Cable shall be #16awg solid Red (+) and Black (-) with twisted
shield cable types listed below or approved by SimplexGrinnell.
Fire lights (strobes) shall be #12awg solid THHN, one Yellow (+) and
one Orange (-). Wire size may be reduced to #14awg solid THHN with
approval of SimplexGrinnell.
Fire Phone Cable shall be #18awg Black (-) and White (+) with twisted
shield, with Brown tape around each end of the cable when made up in a
junction box, cable types listed below or equal approved by
SimplexGrinnell.
Network Cable shall be #18awg solid Black (-) and White (+) and twisted
shield, labeled network cable.
Audio cable shall be #16awg solid Red (+) and Black (-) with twisted
shield, labeled audio cable.
Relay control wiring, Solenoids and Firing Head wiring shall be #14 awg
solid THHN Gray (-) and Brown (+).
Dampers or Doors: #12 THHN Green, White, Black/Red/Blue*
*-Color Black, Red, or Blue are dependent on the breaker location in
power panel. This is 120 volt wiring and will not be in the same conduit
as the 24 volt fire alarm wiring.
Duct Detector Test Switch shall be #14awg THHN one Purple and one
Blue,
The LED shall be a #14 one Black (-) and one Red (+)
2