Architectural and Engineering Design Standards

(avery) #1
Drawing Number
1.6

Single Door - Level 2 - Mag

Date:

UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011

CV

Job Number

Serial Number Drawn By

Project
Documents

Revisions

Drawing Type
Card Access Details

None

Safety & Security Card Access Standards

Ceiling

Structure
To Card Access Panel

½ in flex raceway w/string.

6in

LCK DSM

Device Rough In Requirements

JB

Device Description Opening


PIR / ALM F F

S

1in conduit sleeve into JB from
unsecured side of door
S

JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide
DSM ½ flex raceway from J-Box into the wall down to a ¾ in opening in frame. 6 in from end of door. Coordinate the location on frame and drilling with the GC. F Frame

LCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F Frame

PIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.

Typical Application : Remote Unlock / Schedule Door

48 in AFF

U

U

Located on unsecured side
of door

KEY ¾ conduit raceway from KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide

¾ in conduit raceway w/string.

PTE KEY
Located on secured
side of door

S

S

PTE ¾ conduit raceway from the ceiling to the PTE location. Provide 4sq box in wall with 1G mud ring vertical. S SecuredSide

November 1, 2016