Drawing Number
1.6
Single Door - Level 2 - Mag
Date:
UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011
CV
Job Number
Serial Number Drawn By
Project
Documents
Revisions
Drawing Type
Card Access Details
None
Safety & Security Card Access Standards
Ceiling
Structure
To Card Access Panel
½ in flex raceway w/string.
6in
LCK DSM
Device Rough In Requirements
JB
Device Description Opening
PIR / ALM F F
S
1in conduit sleeve into JB from
unsecured side of door
S
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide
DSM ½ flex raceway from J-Box into the wall down to a ¾ in opening in frame. 6 in from end of door. Coordinate the location on frame and drilling with the GC. F Frame
LCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F Frame
PIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.
Typical Application : Remote Unlock / Schedule Door
48 in AFF
U
U
Located on unsecured side
of door
KEY ¾ conduit raceway from KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
¾ in conduit raceway w/string.
PTE KEY
Located on secured
side of door
S
S
PTE ¾ conduit raceway from the ceiling to the PTE location. Provide 4sq box in wall with 1G mud ring vertical. S SecuredSide
November 1, 2016