Drawing Number
1.11Double Door - Level 3 - Elec PanicsDate:UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011CVJob NumberSerial Number Drawn ByProject
DocumentsRevisionsDrawing Type
Card Access DetailsNoneSafety & Security Card Access StandardsRDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide1in conduit sleeve into JB from
unsecured side of doorCeilingStructureJ
BoxTo Card Access Panel½ in Flex Raceway with pull stringPIR / ALMTo Video SystemDSMEP EPLocated on public
side of doorDevice Rough In Requirements
Device Description Opening
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide
FFFSSDSMFEP
Power
Supply½ in Flex Raceway for EP Only
(Informational Only)SDSM Use PIR / ALM raceway to PIR / ALM Box. Provide a pull wire from this box location to each DSM switch. F Frame
PIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.LCK48 in AFFUUTypical applications : Clinic Door (Scheduled)LCK LCKF FEP ½ flex raceway from power supply to each transfer hinge. This work is shown for coordination of rough ins only. Wiring related to Electrified Panics by EC F FrameLCK ½ flex raceway from PIR into the wall down to the door lock location. Coordinate the location on frame with the GC. F FrameDH alarm is active and door holder circuit is released. Wiring related to DH and EP by EC.Door Holder Circuit is tied to the power supply. EP’s normally retracted unless a fire F CeilingDHPTE
Located on secured
side of doorSSPTE ¾ conduit raceway from the ceiling to the PTE location. Provide 4sq box in wall with 1G mud ring vertical. S SecuredSideRDRSequence
Door will be monitored and alarmed by Software House system if forced or held
open.
Electrified Panics will be retracted during normal operation. Extended during fire
alarm.
Mag Locks will secure the door under normal operation. Mag Locks de-energized
during fire alarm and EP will extend to latch.KSUKEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSideNovember 1, 2016