Architectural and Engineering Design Standards

(avery) #1
Telecommunications Design 17


  1. System Design: Backbone Distribution System


A backbone distribution system is the part of the premises distribution system that provides connection between
telecommunications spaces. Typically connecting between floors and other campus buildings.

A. Backbone Fiber Optic Cabling Type and Quantity:


  1. A new clinic or offsite facility may require ITS fiber optic infrastructure. Coordinate your site plan
    and conduit entrances with both the University of Iowa ITS department as well as HCIS.


Location Fiber Type Strand Count Termination Type

Campus Location
Renovation
(Intrabuilding
Infrastructure)

Singlemode AND Multimode
(OM4)

Min. 24 of each LC-APC and
LC-UPC

New Clinic or Off Site
Facility

Match incoming fiber type Min. 24 LC-UPC

B. Backbone Copper Cabling Type and Quantity:


  1. All telecommunications rooms built out within the campus shall require a backbone voice copper
    backbone cable. Provide a minimum 50-pair Category 3 cable from a coordinated location to the
    new telecommunications room. Cable shall terminate on the wall to a Category 6-rated 110 block

  2. Forty-eight (48) Category 6 cables shall route from a dedicated 48-port patch panel mounted on a
    relay rack to a wall location in the telecommunications room adjacent to the multi-pair voice riser
    cabling. The Category 6 cables shall terminate to a Category 6-rated 110 block. Each pair shall be
    terminated. This will become an administration point and final cross-connect field from horizontal
    cables to the voice riser cabling.

  3. System Design: Horizontal Cabling Systems


This is the portion of the cabling system that extends from the work area outlet to the horizontal cross-connect
(telecommunications rooms) in the appropriate space. This includes: category 6 cabling, telecommunications
outlets/connectors, mechanical terminations and patch cords. It may also include multiuser telecommunications
outlet assemblies. Refer to the appendix for product specific information.
A. Category Cable Type and Quantity


  1. Depending on the location, end-user, and systems scheduled, a minimum of Category 6 shall be
    required. See the table below for each system and the type of cabling to be utilized:


Performance Grade of Cable System Served # of cables

Category 6 Typical Work Area Outlet Min. 2

Category 6A Wireless Access Points Min. 2

Category 6A Shielded Telemetry Varies

Category 6A Shielded HDBase-T/Audio Visual Application Varies