  1. Interior: SDI-100 Grade II, 18ga. faces, seamless edges with 20ga. stiffeners and sound insulation core.

  2. Doors sha ll be templ ate reinf orced for hardware 7ga. on hinges, 12ga. everywhere else.

  3. Acceptable manufacturers: Ceco, Cur ries, Steelcraft, o r Owner approved equal.


08 14 00 Flush Wood Doors


  1. All doors fire rated to less than 90 minutes shall be flush wood do or and be UL fire rated and meet NFPA 80
    standard.

  2. Doors greater than 3’ wide r equire 4 hinges.

  3. In high cart traffic a reas, door s shall have stainless steel kickplates.

  4. Doors shall be solid core particle board, premium grade, pl ain sliced, red oak (or approved finish materal), book-
    matched, 5 pl y, AWI 1300. Optional use of eiDoor Vinyl Clad Interior doors by Eggers, VT Industries, Algoma,
    or approved MFR is pe rmissibl e and app rov ed by owner.

  5. Finished doo rs shall not cont ain k nots.

  6. Lead lined doo rs shall be seven ply, solid particle core with hardwood cross ba nds and lead glued to the core.
    Lead lined door size and lead thickness is de pe ndent on the level of radiation pr otection required. Lead lined
    frames and doors shall be ins talled according to manu facturer’s specifi cations.

  7. Doors s ha ll be p remachine d for hardware and prefitted to net size.

  8. Acceptable manufacturers: G raham, Marshfield, Algoma, Eggers, VT I ndustries, or Owner approv ed e qual.

  9. Mineral core doors are not accepted.


08 31 00 Fire Rated Access Doors
16ga. frame with 20ga. galvanized bonde rized steel panels, UL fire rated, meet NFPA 80 standa rd and must be self-
closing and positive latching. Frame to be trimless, with flush door.


  • Cesco, JL I ndustries, Milcor, or Owne r a pp rov ed e qual.


08 33 23 Rolling Fire Doors
22ga. SS or galvanized steel, interlocking slats, prime painted with automatic closing activated by smoke detection
system, UL fire rated and must meet NFPA 80 and local fire codes. – Cookson FD-5 or Owner approved equal. Tube
motors are preferred.

08 51 13 Aluminum Windows


  1. Interior
    a) Interior aluminum windows shall match existing.
    b) Acceptable manufacturers: Wausau, EFCO, Moduline or Owner approved equal.

  2. Exterior
    a) No w indows shall use integral blinds.
    b) No pivot-type windows shall be us ed.
    c) Extruded aluminum, prime billet 6063 alloy T5 temper.
    d) Anodic finish shall be Architectural Class I, electrolytically deposited minimum thickness 0.7 mil.
    e) Color shall match existing; refer to section 1.7.