Architectural and Engineering Design Standards

(avery) #1

Rev. 13 November 1, 2016


Page | 37


  1. Insulating glass 1” thick composed of ¼” reflective, heat strengthened bronze tint float glass, ½” air space and
    interior lite of ¼” clear float glass.

  2. 5/8” clear laminated heat strengthened float glass.

  3. Acceptable manufacturers: PPG, Ford Glass, Viracon; Wireglass manufacturers: Central
    Glass, Ashai Glass, HJ Martin & Son.

  4. Fire rated glass: TGP “Firelite.”


4.9 Division 09 – Finishes


NOTE: Substitute low or zero volati le organic compound (VOC) paints, stains, adhesives, sealants and other construction materials, where
practical.

09 22 16 Non-Load B earing Partition Framing


  1. Steel stud partitions shall be 20 gauge minimum for interior partitions. Taller walls may require heavier gauge
    studs.


09 29 00 Gypsum Wallboard


  1. To avoid moisture wicking, undercut outer layer of gypsum wallboard by 1/4” at base and caulk with moisture
    resistant caulk that meets fire rating for wall. All gypsum wall board to go to deck or structure above.

  2. In wet areas and areas near sinks and ice machines non-moisture wicking wallboard shall be specified; USG
    FIBEROCK Brand Aqua-Tough Interior Panels or Owner approved equal.

  3. O.R.’s and high abuse areas to relieve impact resistant gypsum board.
    09 50 00 Acoustical Ceilings

  4. Standard tile is 24” x 24” Armstrong Ultima Health Zone, 9/16” Tegular Edge (1936) with 9/16” Suprafine grid or
    approved equivalent.


09 65 00 Resilient Flooring


  1. Resilient flooring to be Nora or approved equal. Nora Plan Envirocare in patient care areas. Inpatient rooms,
    procedure areas, cleanrooms and other places where required to have a 6” integral cove terminated with a cold
    weld against at the wall. Provide (1) #1 Nora Pad for every 10,000 square feet of Envirocare installed.


Nora Norament Grano tiles to be used in main public corridors.



  1. Any patterns must be water jet cut.

  2. All seams to be hot welded.

  3. Acrylic adhesive to be used as a standard. For OR’s and areas with heavy rolling loads, Dryfix is recommended.


09 65 16 Resilient Sheet Flooring


  1. Telecommunications closets shall have VCT floors.
    09 68 16 Rolled Carpet