Hardware Manual

(John Hannent) #1

Saia-Burgess Controls AG


Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Communication interfaces

4


RS 422 with PCD2.F520

Connection diagram for RS 485 line termination resistors

+5 V

/RX-/TX

RX-TX

PCD1.M1xx
PCD2.Mxx0

PCD1.M1xx
PCD2.Mxx0

PCD1.M1xx
PCD2.Mxx0
+5 V

37/
47

/n

36/
46

n n /n

/n

n

PCD2.Mxxx
socket B(1), B2

Pull up
330 Ohm

Pull down
330 Ohm Segment lenght max. 1200 m
max. 32 stations

Termination
Resistor
150 Ohm

At the first and last stations, jumper J1 must be set to the “CLOSED“ position.
At all other stations, jumper J1 must be set to “OPEN” (factory setting)

For installation details, see manual 26 / 740 “Installation components for RS 485“Installation components for RS 485Installation components for RS 485
networks””

The PCD7.F772 Profibus module (details in 4.8.3) and the PCD7.F802 LON module
(details in 4.9) also have an RS 485 interface.
However, these modules are not supported by all PCD1 / PCD2 units.
The wiring is identical to the RS 485 wiring for the PCD2.F520 Modules.

4.6.2 RS 422 with PCD2.F520


RS 422: socket B(1) Port #3

39
38
37
36
35
34
33
32
31
30

PGND

TX

/TX

RX

/RX

SGND

TX

/TX

RX

/RX

J1

OPEN CLOSED

39
38
37
36

34
33
32
31

PCD2.F520

Port # 2RS

232

Port # 3RS 422

Peripheral Cable

Screw
terminal block,
socket B/B1 Socket B(1)
Free download pdf