Saia-Burgess Controls AG
Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Communication interfaces
4
MP-Bus with PCD2.T500
Total power consumption of MFT2 actuators [W]
1
10
100
1000
10000
0 10 20 30 40 50 60 70 80 90 1 00 [W]
0.75 mm1.5 mm 22 1.0 mm2.5 mm^22
Kabellänge [m]
Cable length vs true watts applies to DC supply
(minimum supply voltage 24.0 VDC)
The following can be read from the family of curves:
- Cable with conductor 0.75 mm² gives: Cable length 60 m
- Cable with conductor 1.0 mm² gives: Cable length 80 m
- Cable with conductor 1.5 mm² gives: Cable length 115 m
- Cable with conductor 2.5 mm² gives: Cable length 200 m
4.10.10 Maximum line length for 24 VAC supply (in situ)
6 4/5 1 2 5 1 2 5 1 2 5
Masse
MP
PCD2.T500
Maximum line length for 24 VDC supply
24 VAC
Drive
1
Drive
2
Drive
8
24 VAC 24 VAC
If the actuators are supplied locally with 24 VAC via a separate transformer, line
lengths can be much increased. Regardless of the power ratings for the actuators
connected, the line lengths will be according to the following table.
Conductor Ø L = max. line length
0.75 mm² 800 m
1.0 mm² 800 m
1.5 mm² 800 m
2.5 mm² 800 m