Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.E110, PCD2.E111, PCD2.E113 and PCD2.E116Input/output (I/O) modules5
Input circuits and terminal designation
Depending on external wiring, this module may be used for source or sink operation.
Source operation (positive logic):E1
4k74k710k10kE0
1 0
L9 8
E1E0I/O
Bus
Inter-
face
PCD BusUe : 24 VDC
12 VDC
5 VDCLoad resistors Input filter Threshold
switch
LEDSwitch closed
(positive at input) : Input state "H" = LED on
Switch open : Input state "L" = LED offSink operation (negative logic):E00
E11
L9 8
Switch closed
(negative at input) : Input state "L" = LED off
Ue : 24 V 12 VDCDC Switch open : Input state "H" = LED on
5 VDCWatchdog: This module can be used on all base addresses; there is no interaction
with the watchdog on the CPUs. For details, please refer to the “Watchdog” section,
which describes the correct use of the watchdog in conjunction with PCD2 compo-
nents.