Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-


Saia-Burgess Controls AG


General technical details

CPUs and expansion housings

3


3.2 General technical details


Supply (external and internal)
Supply voltage
(according EN / IEC 61 131-2)

24 VDC -20 / +25% incl. 5% ripples

Power consumption1) PCD1 and PCD2: typically 625 mA / 15 W for 64 I/Os
PCD2: typically 833 mA / 20 W for 128 I/Os
Capacity of internal
5 V bus2)

PCD1: 750 mA
PCD2.M110/M120 hardware version <H: 1100 mA
PCD2.M110/M120 hardware version >=H: 1600 mA
PCD2.M150: 1600 mA
PCD2.M170: 1600 mA
PCD2.M480: 2000 mA
Capacity of internal +V bus
(16...24 V)2)

PCD1: 100 mA
PCD2: 200 mA
Short voltage interruptions
(according EN / IEC 61 131-2))

≤ 10 ms with interval ≥ 1 s

1) The loads on the outputs are generally more significant for sizing the supply than the internal power leakage
within the controller
2) When planning PCD2 systems, it is essential to check that the two internal supplies are not overloaded. This
check is especially important where analogue, counter and motion control modules are used, as these may con-
sume a lot of power.

Atmospheric conditions
Ambient
temperature

Mounting on vertical surface with vertically aligned connection
terminals: 0 ... +55 °C
In all other mounting positions, a reduced temperature range of
0 ... +40 °C applies
Storage temperature -20 ... +85 °C (DIN 40 040, class HS)
Relative humidity 30 ... 95% without condensation (DIN 40 040, class F)

Vibration resistance
Vibration according to EN/IEC 61 131-2:
5 ... 13.2 Hz constant amplitude 1.42 mm
13.2 ... 150 Hz, constant acceleration (simple gravitational
acceleration)

Electrical safety
Protection type IP 20 according to EN 60 529
Air/leakage paths according to DIN EN 61 131-2 and DIN EN 50 178: between
circuits and bodies and between electrically isolated circuits:
surge category II, fouling level 2
Test voltage 350 V / 50Hz AC for nominal unit voltage 24 VDC

Electromagnetic compatibility
Electrostatic discharge according to EN 61 000-4-2: 8 kV: air discharge
8 kV: contact discharge
Electromagnetic fields according to EN 61 000-4-3: field intensity 10 V/m,
80 ... 1000 MHz
Bursts according to EN 61 000-4-4: 4 kV on DC supply lines,
1/2 kV on I/O signal lines,
1 kV on interface lines
Noise emission PCD1,
PCD2.M110/M120/M

according to EN 50 081-1: Class B (residential areas)