Hardware Manual

(John Hannent) #1

Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-


Saia-Burgess Controls AG


General technical details

CPUs and expansion housings

3


Noise emission
PCD2.M150/M

according to EN 50 081-2: Class A (for industrial areas)
Guidance on the correct use of these controls in residential
areas can be found at http://www.sbc-support.ch (additional
measures).
Noise immunity PCD1/
PCD

according to EN 50 082-

Mechanism and mounting
Housing material Base:
Cover:
Fibre optics: PC, crystal-clear
Mounting rail Double top-hat rail as per EN 50022-35 (2 x 35 mm)

Connections
Screw terminals Unless specified otherwise: for wires of 1.5 mm^2 (AWG 16) or
2 x 0.5 mm^2 (2 x AWG 20)
Plug-in screw terminals The terminal block may only be plugged onto 20 times. It must
then be replaced, to guarantee a reliable contact

Standards / approvals
EN/IEC 61 131-
VDE (PCD1 and
PCD2.M110/M120/M
only)

0160


Shipbuilding Germanischer Lloyd, Lloyd’s Register of Shipping, Det Norske
Veritas, Polski Rejestr Statków
UL-USA, UL-CDN Please note the following conditions for UL-compliant use:
Wiring: temperature: 60/75 °C, thermoplastic insulated Cu wires
Terminal tightening torque: 0.5 Nm