Hardware Manual

(John Hannent) #1

Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Saia-Burgess Controls AG


PCD2.W10x

Input/output (I/O) modules

5


Wiring for negative unipolar analogue inputs

+E


  • E


(PGND)
PCD 2 .W 105 : 100 Ohm / 0. 1 %

All unused inputs must be earthed.

Output circuits and terminal designation

ANALOGUE INPUTS

I/O

Bu

s

DATA

READ

WRITE

PC

D^

Bu

s

+ 5 V
GND
+ 24 V

DATA

CHANNEL SELECTION
START CONVERSION

A

D 12 BITS

BUSY FLAG

Bipolar
Offset

UNIPOLAR

MUX GAIN BIPOLAR
Input
Offset

+-EE (^00) GAIN = 1 ... 5 (SET/RES O 2 )
+E 1



  • E 1


+E 2


  • E 2
    +E 3

  • E 3


0 1 2 3 4 5 6 7 8 9

V+ + 15 V


  • 15 V


DCDC

Shunt for Current version

Programming
Classic: Programming examples for the PCD2.W10x can be found in a separate
manual and on the TCS Support site (www.sbc-support.ch + getting started).
xx7: the firmware reads in the values according to the configuration (I/O Builder)

Watchdog: This module cannot be used on the base address 240 (or 496 for the
PCD2.M17x), because it would interact with the watchdog, and would cause a
malfunction.

For details, please refer to the “Watchdog” section, which describes the correct use of
the watchdog in conjunction with PCD2 components.