Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W2x0
Input/output (I/O) modules
5
Terminals
Bus connector
Bus interface
Reference voltage (and source)
A/D converter and multiplexer
Input filter
Screw terminals
9 8 7 6 5 4 3 2 1 0
E 76 5 4 3 2 1 E 0
Digital/analogue values
Input signals and type Digital values
PCD2.W200 PCD2.W210 PCD2.W220 Classic xx7 Simatic
+ 10.0 V + 20 mA Calculate the
appropriate
values with the
formulae at
the end of this
section
1023 1023 27648
+ 5.0 V + 10 mA 512 512 13824
+ 4 mA 205 205 5530
0 V 0 mA 0 0 0
- 10.0 V – 20 mA 0 0 0
Connection concept PCD2.W200
9 8 7 6 5 4 3 2 1 0
- E7 E6 E5 E4 E3 E2 E1 E0
Earthing bar
max.
20 cm
0...10 V for PCD2.W200
Shield
Signalsource
Signalsource
Signalsource
Signalsource