Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W2x0
Input/output (I/O) modules
5
Block diagram
INPUT FILTER
E0
E1
E2
E3
E4
E5
E6
ANALOGUE INPUTSE7
MUX
A
D
BUSY (adr. 15)
DATA OUT
10 bits serial
A/D act. (addr. 15)
Clock
Channel address 0.. 7
I/O Bus
DATA
READ
WRITE
ADDR PCD Bus
+5 V
GND
+24 V
Voltage
Source
10.000 V
7K5
GND
Ref.
Voltage
2.500 V
..W220 only
Watchdog: This module cannot be used on the base address 240 (or 496 for the
PCD2.M170), because it would interact with the watchdog, and would cause a
malfunction.
For details, please refer to the “Watchdog” section, which describes the correct use
of the watchdog in conjunction with PCD2 components.